Effect of the Chem-Free Purification Systems HVAC
Ozone/Ultraviolet Light Unit on the Survival of Molds in an Air Duct

August 30, 2003
Prepared for
Alpha Magnetics By
Kerby F Fannin, M.P.H., Ph.D., CES
Certified Environmental Specialist


1.0 Introduction

1.1 Purpose
The purpose of these tests was to determine the effect of the Chem-Free Purification Systems HVAC
Ozone/Germicidal Ultraviolet Light Unit on the survival of molds suspended in an air duct.

1.2 Background
Air is an important vehicle for transmitting infectious and allergenic molds. Their growth and survival in air ducts provide a contaminating source that offers the opportunity for the dispersion of spores into the air of occupied spaces. In addition, some molds produce mycotoxins that can also be dispersed into occupied spaces as gaseous contaminants that are not removed even by high-efficiency particulate air filtration. Some mycotoxins cause serious health effects in susceptible individuals, with significant long-term effects on vital organs. Reducing the levels of viable molds in air ducts can the lower exposure of susceptible persons to infectious, allergenic, and toxic airborne contaminants in occupied spaces. Levels of viable airborne molds and mycotoxins can be reduced by reducing their ability to survive in contaminated sources, such as in heating, cooling, or ventilating ducts and related equipment.

1.3 Specific Objectives
The specific objective of the tests described herein was to determine the effect the Chem-Free Purification Systems HVAC Ozone/Germicidal Ultraviolet Light Unit on the survival of molds in an air duct.

1.4 Test Microorganisms
A mold species was selected for testing which represents a broad class of commonly encountered molds found in indoor environments. Penicilliumfuniculosum was used to determine the effect of the test unit on the survival of molds in air ducts. This mold has been used extensively in studies of effects of environmental factors on mold survival. De,?icillium funiculosum has been used, for example, as a model organism to evaluate the effects of aerial disinfection of libraries.i The mold is widely used for testing the survival of molds in the environment. It is also representative of broader classes of molds that demonstrate allergenic and/or pathogenic reactions in exposed humans.

i Malalanirina W. Rakotonirainy et a!., “Research on Fungicides for Aerial Disinfection by Thermal logging in Libraries and Archives,” International Biodeterioration & Biodegradation, /999, 44. pp. 133-1 39.

2.0 Test Equipment and Methods

2.1 Test Unit
The test unit was described as the Chem-Free Purffication systems HVAC Ozone/Germicidal Ultraviolet Light Unit. The unit was duct mounted and contained a germicidal light, as well as an ozone-producing light, which was shielded from a germicidal ultraviolet light in order to prevent the UV light from destroying the ozone produced by the other 184 nm ozone-producing light..

2.2 Test Duct
The test duct consisted of an electrically grounded galvanized steel ventilation duct with a dimension of 10-inch by 16-inch by 12 feet. The duct was attached I x 2 x 2.5 feet HEPA-filtered Air-Kleen air-moving device. Using transitional adapters the test duct was attached to approximately 21 feet x 10-inch diameter galvanized steel recirculation duct. Air was circulated through the test duct using two backward curved impellers. Air was recirculated through the test portion of the air duct at an average face velocity of approximately 240- feet per minute (!j

2.3 Environmental Conditions
The relative humidity and temperature were measured using a wet and dry bulb psychrometer. These experiments were performed at a relative humidity level of 64 % and a temperature of 80° F. Mold growth in indoor environments is favored by high relative humidity levels. Ozone is also generally more germicidally active at high relative humidity levels. These tests were performed under ambient conditions in an occupied commercial structure.

2.4 In-Duct Microorganism-Suspending Holders
The tests were performed using sterile membrane filter (Gelman Sciences) test surfaces inoculated with the test microorganisms. The inoculated filters were placed onto aluminum in-duct suspending holders and attached using cellophane tape.

2.5 Air Velocity
Air velocity measurements were performed with a thermal anemometer Model 9870 Alnor Air Velocity Meter.

2.6 Mold Test Methods
Penicillium Juniculosum (ATCC 11797) was grown on potato dextrose agar (Difco) at 24° C. Ten- fold dilutions of the organism cultures were made in phosphate buffered water. Selected dilutions of the test organisms were inoculated onto the test filters using a membrane filtration procedure and rinsed with phosphate buffered water. Inoculated filters were aseptically placed onto the surface of the mold-suspending holders and secured on one edge using adhesive tape. The air duct under controlled air velocity conditions for a specified duration of time. The control experiments were performed with the test unit suspending into the air duct, hut in a non-energized condition. The test experiments were performed with the test unit in an energized condition. Following exposure to specified conditions, the inoculated membrane filters were aseptically removed trom the surface of the mold-suspending holders using sterile forceps. The inoculated membrane filters were then placed onto the surface of potato dextrose agar-containing petri dishes for assay. Colonies were counted and the cultures were photographed following four and then five days of incubation at room temperature.

3.0 Results

The control experiment, which was performed without the test unit operating. showed 7 surviving colony forming units (CFU) after the 4- mm exposure time in the air. The test experiment was performed under the same conditions, but with the test unit operating. The test demonstrated 0, (zero) surviving mold CFU.
Penicillium/iiniculosum CFU were too numerous to count. (The culture also showed evidence of the presence of other contaminating molds in the test duct.) Based on counts obtained in other dilutions, the number of CFU was calculated to be 750 CFU. The culture obtained following the same in-duct exposure, but with the test unit operating showed the presence of a sparse number of CFU. To further enumerate the surviving mold CFIJ in the tests, the cultures were incubated for a total of five days. Penicilliumfuniculosum survived a 4-mm exposure to the test unit in the air duct. Based on these results the mold CFU reduction caused by the test unit exceeded 99.99 per cent under the conditions of these tests.

4.0 Summary and Conclusions

A series of tests were performed on a HVAC duct-mounted Chem-Free Purification Systems IIVAC Ozone/Germicidal unit, referred to as the test unit. The test mold used for these tests, Penicillium funiculosum, was a penicillin mold that was representative of common mold contaminants in indoor environments. The survival of the molds in the air duct is likely to be affected by the specific environmental conditions and the duration of exposure. Under the conditions of these experiments, which represented the indoor conditions in an occupied area, the test unit was found to reduce the survival of Penicillium jiiniculosum molds by 99.99 percent following exposure in an air duct at a distance of 39 inches for 4- mm.


READ TEST RESULTS

Effect of the Chem-Free Purification Systems HVAC
Ozone/Ultraviolet Light Unit on the Survival of Molds in an Air Duct
Prepared for
Alpha Magnetics By
Kerby F Fannin, M.P.H., Ph.D., CES
Certified Environmental Specialist
• Small, 13”L x 4”W x 3.5”T

• Light weight, 2.5 pounds.

• Portable, with handle and feet.

• Two “Key slots” on bottom for fixed mounting on bulkhead.

• 12 Volts DC, 1.0 Amp of power.

• Distributes ozone into free air with a small, very quiet 13 CFM fan.

• Built in 24-hour timer with 12-hour clock face and a minimum on-off cycle time of 15 minutes.

• Supplied with cigarette lighter, or “Power point” plug.

• Optional 115 VAC — 12 VDC converter available.


Ozone — “Natures Purifier’
Ozone was first discovered in Germany in 1840. Subsequent research revealed that ozone was a “Tn-atomic” allotrope of oxygen (made from three atoms of oxygen) that was an exceptionally powerful oxidizer. Ozone is produced naturally in the atmosphere by UV radiation in sunlight, and by lightning. The primary benefit to all surface life forms on the Earth is the absorption of virtually all of the Ultraviolet radiation emitted by the Sun. If all, or even most, of the UV radiation were to reach the Earth’s surface, all life forms would be killed. Another benefit derived from ozone is the purification of the air we breathe. Our DC & is portable ozone at its best.